Schneider Electric BDA24080Y2

Schneider Electric I-Lineâ„¢ PowerPactâ„¢ BDA24080Y2 Molded Case Circuit Breaker, 480Y/277 V AC, 80 A, 25 kA at 240 V AC, 18 kA at 480 V AC, 14 kA at 600Y/347 V AC Interrupt, 2 Poles, Thermal Magnetic Trip

Brand: Schneider Electric

Item ID: 579505

MPN: BDA24080Y2

Login for Price

Features

  • Available in 1, 2, 3, and 4 pole for unit mounts
  • Dual rated AC/DC with 3 levels of breaking capacity
  • A wide range of accessories, auxiliaries, and lug connections available

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 80A, 2 pole, circuit breaker has a breaking capacity of 18kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with an AC phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.

Schneider Electric PowerPacT B BDA24080Y2 I-Line circuit breaker, 80A, 2-pole, 480Y/277VAC, 18kA interrupt rating at 480Y/277VAC, thermal-magnetic trip and 80% continuous-current rating.

California residents see Prop 65 WARNINGS

Specifications

Actuator Type

Toggle

Amperage Rating

80 A

Color

Gray

Connection Type

Line/Load Lug

Dimensions

5.39 in H x 2.12 in W x 4.01 in D

Enclosure Type

NEMA AB4/IP40

Frame

B

Frequency Rating

50/60 Hz

Interrupt Rating

25 kA at 240 VAC, 18 kA at 480 VAC, 14 kA at 600Y/347 VAC

Mounting Type

DIN Rail/Threaded

Number of Poles

2

Temperature Rating

-13 to 158 deg F

Trip Range

800 to 1200 A

Trip Type

Thermal Magnetic

Voltage Rating

480Y/277 V AC

Wire Size

14 to 2/0 AWG Al/Cu

Standard Approval

CSA C22.2 No 5|CE Certified|CCC Certified|EAC Certified|EN/IEC 60947-2, 60947-5-1|GB 14048.2|NOM Certified|UL 489|PROP65: WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.p65warnings.ca.gov

Application

Industrial Control Panels, Commercial OEM, Electrical Distribution Equipment, Commercial Building and Industrial Building Applications

Documentation

-engineer BDA24080Y2 Drawing https://externalassets.unilogcorp.com/ASSETS/DOCUMENTS/ITEMS/EN/Schneider_Electric_BDA24080Y2_Full_Engineering_Drawing.pdf

Schneider Electric PowerPacT B-Frame Circuit Breaker User Manual https://externalassets.unilogcorp.com/ASSETS/DOCUMENTS/ITEMS/EN/Square_D_B075_User_Manual.pdf

Schneider Electric BDA24080Y2 PowerPacT B Circuit Breaker RoHS Compliance Declaration https://externalassets.unilogcorp.com/ASSETS/DOCUMENTS/ITEMS/EN/Schneider_Electric_BDA24080Y2_RoHS.pdf

Schneider Electric BDA24080Y2 PowerPacT B Circuit Breaker Specification Sheet https://externalassets.unilogcorp.com/ASSETS/DOCUMENTS/ITEMS/EN/Schneider_Electric_BDA24080Y2_Specification_Sheet.pdf

videoInstalling PowerPacT B-Frame Breakers onto a DIN Rail https://www.youtube.com/watch?v=xNQHMcmA6OE

Schneider Electric BDA24080Y2